Installation Height And Location Selection Requirements For Ground-mounted Stainless Steel Distribution Boxes

Date: Read: 8

According to the "Code for Acceptance of Construction Quality of Building Electrical Engineering" GB50303-2002, the vertical distance between the bottom surface of the fixed stainless steel enclosure ip67 and the ground should be greater than 1.3 meters and less than 1.5 meters. The bottom surface of the mobile stainless steel irrigation controller enclosure should be more than 0.6 meters and less than 1.5 meters above the ground. This height setting fully considers the ergonomic characteristics of operators, allowing routine maintenance work such as switch operation, circuit inspection, and instrument reading to be completed from a comfortable position.

When the stainless steel junction box price is installed on a wall, the bottom opening of the enclosure is typically between 1.2 meters and 1.5 meters from the ground. Within the same building, the installation height of the same type stainless steel printer enclosure should be consistent, with an allowable deviation within 10 millimeters. This uniformity is not only aesthetically pleasing but also facilitates later systematic management.

Choosing a suitable installation location requires comprehensive consideration of multiple factors. The stainless steel surface mount electrical box should be installed in a safe, dry, well-ventilated, and easily accessible location. Sufficient operating space must be reserved around the stainless steel waterproof junction box, at least enough to accommodate two people working simultaneously, and the passageway width should meet the needs of maintenance and emergency handling.

steel terminal box must not be installed in environments with severely corrosive gases, vapors, liquids, or other harmful media. If use in a special environment is unavoidable, specific protective measures must be taken. Locations susceptible to impact from solid objects, strong vibrations, liquid splashes, and heat sources should also be avoided.

In areas with concentrated loads, strong box stainless steel enclosures should be installed as close as possible to the electrical equipment. The distance between the distribution box and the switch box should not exceed 30 meters, and the horizontal distance between the switch box and the fixed electrical equipment it controls should not exceed 3 meters. This proximity principle reduces line losses and improves power supply efficiency.

Installation Height And Location Selection Requirements For Ground-mounted Stainless Steel Distribution Boxes